| 500 kVA Resistive/Reactive |
1.875 MVA Resistive/Reactive |
3.3 MVA Resistive/Reactive |
6.25 MVA Resistive/Reactive |
| Downloads | 500 kVA specsheet | 1.875 MVA specsheet | 3.3 MVA specsheet | 6.25 MVA specsheet |
| Manufacturer | Crestchic UK | Crestchic UK | Crestchic UK | Crestchic UK |
| Power Range | 50Hz - 60Hz | 50Hz - 60Hz | 50Hz - 60Hz | 50Hz - 60Hz |
| Footprint | 5' x 4' ISO Container | 6' x 8' ISO Container | 10' x 8' ISO Container | 20' x 8' ISO Container |
| Capcity | 500 kVA/400 KW @ 480 volts, 60 Hz, 3 phase, 0.8 PF units are linkable for larger loads | 1.875 MVA/1500 KW @ 480 volts, 60 Hz, 3 phase, 0.8 PF units are linkable for larger loads | 3.3 MVA/2640 KW @ 480 volts, 60 Hz, 3 phase, 0.8 PF units are linkable for larger loads | 6.25 MVA/5000 KW @ 480 volts, 60 Hz, 3 phase, 0.8 PF units are linkable for larger loads |
| Design Voltage | 480 volts, 60 Hz; may be used in lower voltages and 50 Hz at reduced capacity | 480 volts, 60 Hz; may be used in lower voltages and 50 Hz at reduced capacity | 480 volts, 60 Hz; may be used in lower voltages and 50 Hz at reduced capacity | 480 volts, 60 Hz; may be used in lower voltages and 50 Hz at reduced capacity |
| Minimum Load Steps | 1kW, 1kVAR | 1kW, 1kVAR | 1kW, 1kVAR | 1kW, 1kVAR |
| Control System | Hand-held, PC, or manual control systems | Hand-held, PC, or manual control systems | Hand-held, PC, or manual control systems | Hand-held, PC, or manual control systems |
| Ambient Parameters | Maintains maximum capacity in ambient conditions up to 120° F | Maintains maximum capacity in ambient conditions up to 120° F | Maintains maximum capacity in ambient conditions up to 120° F | Maintains maximum capacity in ambient conditions up to 120° F |
| Fan and Control Power | Via main bus or 20 amp, 480 volt, 3 phase external source | Via main bus or 30 amp, 480 volt, 3 phase external source | Via main bus or 70 amp, 480 volt, 3 phase external source | Via main bus or 100 amp, 480 volt, 3 phase external source |
| Air Flow | Side intake, top exhaust | Side intake, top exhaust | Side intake, top exhaust | Side intake, top exhaust |
| Enclosures | 5' ISO weatherproof container | 6' ISO weatherproof container | 10' ISO weatherproof container | 20' ISO weatherproof container |
| Dimensions | 500 kVA - Height: 6.5' Width: 4.0', Length: 5.0' Weight: 4,800 lbs. | 1.875 MVA - Height: 8.5' Width: 6.23', Length: 8.0' Weight: 13,200 lbs. | 3.3 MVA - Height: 8.5' Width: 8.0', Length: 10.0' Weight: 22,500 lbs. | 6.25 MVA - Height: 8.5' Width: 8.0', Length: 20.0' Weight: 38,376 lbs. |